Proper Installation Of Cold Storage Sandwich Panels

Jul 16, 2026

Leave a message

To meet the specific requirements for thermal insulation, thermal bridge prevention, and sealing in cold storage sandwich panels, installation must strictly adhere to industry standards. Key operational points are as follows:

 

Pre-installation Preparation
Material Verification: Check parameters such as panel thickness and core material density to ensure compliance with the *Technical Specification for Metal-Faced Insulated Sandwich Panels for Cold Storage Engineering*; spot-check thickness after the panels have been stored for over 24 hours.
Site and Foundation Preparation: Ensure the construction site is dry and well-ventilated; level the site in advance and cast a concrete foundation or lay channel steel ground beams, keeping the floor level deviation within 5mm.
Plan Formulation: Develop a specialized construction plan based on construction drawings, clearly outlining the panel layout and the arrangement of support and fixing structures.
Panel Storage: Implement fire, wind, and waterproofing measures at the storage site and keep panels away from heat and ignition sources; rock wool sandwich panels must be covered to protect against rain.

 

Core Installation Process
Framework Positioning: Mark the starting line; first fix the U-shaped channels or vertical columns, then install ground beams and ring beams, using a level to constantly verify column verticality (deviation must not exceed 1/1000).
Wall Panel Installation: Starting from a corner of the cold storage unit, fit the sandwich panels into the U-shaped channel from bottom to top, ensuring tight interlocking of male and female joints; do not force-hammer joints, as this causes deformation.
Roof Panel Installation: Install pre-cambered T-shaped iron supports in advance; rest the longitudinal ends of the panels on the wall panels and T-shaped irons respectively; secure with rivets after adjusting for parallelism, verticality, and elevation.
Panel Joint Treatment: For horizontal joints, apply sealant inside the inner and outer tongue-and-groove connections and press the joints tight to eliminate core material gaps; for longitudinal connections, leave a gap of at least 20mm, fill with polyurethane, and seal with accessory caps.
Corners and Special Junctions: Ensure butt joints at corners and T-junctions are flush and tight; fill gaps with polyurethane and seal them, ensuring there are no visible depressions or warping at corner coverings.